User Guide
IM/L160_6
Wall-/Pipe-mount Level Indicator
L160
GETTING STARTED
This manual is divided into five sections which contain all the information needed to
install, configure, commission and operate the DATUM L160. Each section is
identified clearly by a symbol as shown below.
Displays and Controls
•
•
•
Displays and function keys
LED indication
Error messages
Operator Mode (Level 1)
Operator menus for:
•
–
–
–
Standard level indicator
Maximum/minimum/average level indicator
Level indicator with volume indication
Set Up Mode (Level 2)
•
•
Alarm trip points
Alarm hysteresis levels
8
Configuration Mode (Levels 3 and 4)
•
•
Accessing the configuration levels
Level 3
–
–
–
–
Hardware assignment and input type
Alarm types and hysteresis
Operator functions
Digital input and serial communications
•
Level 4
Ranges and passwords
–
Installation
•
•
•
Siting
Mounting
Electrical connections
Symbol Identification and Section Contents
1
CONTENTS
1
DISPLAYS AND FUNCTION KEYS ...............................................................3
1.1 Introduction ............................................................................................3
1.2 Use of Function Keys .............................................................................4
1.3 LED Alarms and Indicators .....................................................................5
1.4 Error Messages ......................................................................................6
2
OPERATOR MODE ........................................................................................7
2.1 Introduction ............................................................................................7
2.2 Operating Page – Standard (Level 1) ......................................................8
2.3 Operating Page – Max./Min./Average Functions (Level 1) .......................9
2.4 Operating Page – Volume Function (Level 1) ........................................11
3
4
SET UP MODE .............................................................................................12
3.1 Introduction ..........................................................................................12
3.2 Set Up Level (Level 2) ..........................................................................13
CONFIGURATION MODE ........................................................................... 16
4.1 Introduction ..........................................................................................16
4.2 Accessing the Configuration Mode .......................................................18
4.3 Basic Hardware and Indicator Functions (Level 3) ................................18
4.4 Ranges and Passwords (Level 4)..........................................................28
5
INSTALLATION ............................................................................................30
5.1 Siting the System .................................................................................31
5.2 Siting the Instrment ..............................................................................32
5.3 Mounting the Instrument ......................................................................34
5.4 Electrical Connections ..........................................................................36
5.5 Relays, Arc Suppression, Outputs and Input ........................................38
SPECIFICATION ...................................................................................................39
Note.
The fold-out page attached to the back cover of this manual
shows all frames in the programming levels. Space is
provided next to each frame to record programmed
settings/selections.
2
1
DISPLAYS AND FUNCTION KEYS
1.1 Introduction – Fig. 1.1
The DATUM L160 front panel display, function keys and LED indicators are shown in
Fig. 1.1.
A1
Alarm LEDs
(secret-till-lit)
A2
Display
A3
tESt
Displays shown during
the start up procedure
Function Keys
Parameter advance
A1
A2
tESt
A3
Displayed at startup
for 3 seconds
Raise
Lower
A1
A2
200101
A3
Software version and issue
eg. L160/2001, Issue 1
(displayed for 3 seconds)
Multi-function key
Fig. 1.1 Front Panel Display, Function Keys and Indicators
3
…1 DISPLAYS AND FUNCTION KEYS
1.2 Use of Function Keys – Fig. 1.2
A – Raise and Lower Keys
+
–
1000
1001
999
LEVEL2
Use to change/set a parameter value…
or…
LEVEL1
…move between levels
B – Parameter Advance Key
Frame 1
(top of level)
LEVEL1
LEVELx
1001
2002
Frame 2
or…
1001
3003
4 004
Press for
a few
seconds
Use to advance to the next
frame within a level…
…select the top (LEVEL)
frame from within a level
Note. This key also stores any changes made in the previous frame
C – Multi-function Key
CodE
1234 56
0
Use to view a parameter setting or selection…or…
…select individual
characters in a frame
Fig. 1.2 Use of Function Keys
4
1
DISPLAYS AND FUNCTION KEYS…
1.3 LED Alarms and Indicators – Fig. 1.3
Alarm LEDs
A1
A2
A3
Alarm 1
Alarm 2
Alarm 3
LED
Status
All flashing
Level indicator is in the configuration mode
– see Section 4.2
A1, A2 and A3
Flashes when Alarm is active (off when inactive)
Lit constantly when Alarm is an active, latched alarm
which has been acknowledged
Fig. 1.3 LED Alarms and Indicators
5
…1 DISPLAYS AND FUNCTION KEYS
1.4 Error Messages
Error/Action
To Clear Display
Display
Start-up Screen
Displayed at system start-up.
tESt
Clears automatically
(after 3 secs.) to display
software version/issue
– see Fig. 1.1.
Calibration error
CALErr
CFGErr
Turn mains power off and on again
(if the error persists contact the
Service Organization).
Press the
Press the
key.
key.
Configuration error
The configuration and/or setup data
for the instrument is corrupted. Turn
mains power off and on again
(if the error persists, check
configuration/setup settings).
A to D Converter fault
The analog to digital converter is
not communicating correctly.
Ad Err
Turn mains power off and
on again. If the fault
persists, contact the
Service Organization.
Sensor input out of range
Restore valid sensor input.
Check sensor output.
IPFAIL
OPtErr
Option board error
Communications to the option
board have failed.
Contact the Service
Organization.
6
2
OPERATOR MODE
2.1 Introduction
Operator Mode (Level 1) is the normal day-to-day mode of the DATUM L160.
Frames displayed in Level 1 are determined and limited by the indicator functions
which are selected during configuration of the instrument – see Section 4.
Note. Only the operating frames relevant to the configured functions are
displayed in Operator Mode.
The three indicator functions are:
•
•
•
Standard Level Indicator
–
–
–
page 8
page 9
page 11
Level Indicator with Max./Min./Average
Level Indicator with Volume Indication
7
…2 OPERATOR MODE
2.2 Operating Page – Standard (Level 1)
Process Variable
214 53
Normally displayed in engineering
214 53
units.
To view the input value (in electrical
126
units) press the
key.
UN-ACK•1
Global Alarm Acknowledge (latch alarms only)
UN-ACK
ACK
–
–
alarm unacknowledged
alarm acknowledged
Specific Gravity
This is the value of specific gravity currently being
applied to the process variable (display only).
G1000
CodE
Security Code
Enter the password to access the Set Up Level
(Level 2) or the Configuration Level (Levels 3 and 4).
The default code is 0.
----
[0 to 9999]
Level 1
LEVEL1
Note. To select this frame from anywhere in this level,
press and hold the
key for a few seconds.
•1 Displayed only if there is an active latch alarm.
8
2
OPERATOR MODE…
2.3 Operating Page – Max./Min./Average Functions (Level 1)
See Section 4.3.3 for details of Max./Min./Average functions.
Measured Level
214 53
To view the input value (in electrical units) press the
key.
Global Alarm Acknowledge (latch alarms only)
UN-ACK
UN-ACK
ACK
–
–
alarm unacknowledged
alarm acknowledged
A 14 05•1
rSt-n
Average Value
This is the mean average value of the process variable,
since the average was reset.
To reset the average value, select rSt-Ythen press
the
key.
rSt-Y
rSt-n
–
–
reset
do not reset
H 1502
Continued on next page.
•1 The average value is displayed only if enabled in the configuration level
– see Section 4.3.3
The average value is reset automatically on power-up and can also be reset from
a digital input – see Section 4.3.4.
9
…2 OPERATOR MODE
…2.3 Operating Page – Max./Min./Average Functions (Level 1)
•1
Maximum Value
This is the maximum value of the process variable since
H 1502
the maximum was reset.
To reset the maximum value, select rSt-Ythen press
rSt-n
the
key.
rSt-Y
rSt-n
–
–
reset
do not reset
•1
Minimum Value
This is the minimum value of the process variable
since the minimum was reset.
L1308
To reset the minimum value, select rSt-Ythen press
the
key.
rSt-Y
rSt-n
rSt-n
–
–
reset
do not reset
Specific Gravity
This is the value of specific gravity currently being
applied to the process variable (display only).
G1000
CodE
------
LEVEL1
Security Code
Enter the correct code to access the Set Up Level
(Level 2) or the Configuration Level (levels 3 and 4).
[0 to 9999]
Level 1
Note. To select this frame from anywhere in this page,
press the
key for a few seconds.
•1 The maximum and minimum values are reset automatically on power-up and can
also be reset from a digital input – see Section 4.3.4.
10
2
OPERATOR MODE…
2.4 Operating Page – Volume Function (Level 1)
Process Variable
214 53
Normally displayed in engineering
214 53
units.
To view the input value (in electrical
126
units) press the
key.
UN-ACK•1
Global Alarm Acknowledge (latch alarms only)
UN-ACK
ACK
–
–
alarm unacknowledged
alarm acknowledged
Specific Gravity
This is the value of specific gravity currently being
applied to the process variable (display only).
G1000
Volume
V23120
CodE
This is the current volume derived from the process
variable.
Security Code
Enter the correct code to access the Set Up Level
(Level 2) or the Configuration Level (Levels 3 and 4).
The default/factory-set code is 0.
[0 to 9999]
----
Level 1
LEVEL1
Note. To select this frame from anywhere in this level,
press the
key for a few seconds.
•1 Displayed only if there is an active latch alarm.
11
8
3
SET UP MODE
3.1 Introduction
To access the Set Up Level (Level 2) the correct code must be entered in the security
code frame (CodE) in Level 1 – see Sections 2.2 to 2.4.
Level 2 – Set Up
LEVEL2
Level 1 –
Operating Level
Alarm 1 Trip Point
A1xx
Correct
Code
LEVEL1
Alarm 1 Hysteresis
Alarm 2 Trip Point
Alarm 2 Hysteresis
Alarm 3 Trip Point
Alarm 3 Hysteresis
Average Value
A1 HYSt
A2xx
CodE x
A2 HYSt
A3xx
Security Code 0 to 9999
(default/factory-set code = 0)
A3 HYSt
A xxxx
H xxxx
L xxxx
SPGrAV
0AdJ
Maximum Value
Minimum Value
Specific Gravity
Offset Adjustment
Fig. 3.1 Accessing the Set Up Level (Level 2)
12
8
3
SET UP MODE…
3.2 Set Up Level (Level 2)
Level 2
LEVEL2
Note. To select this frame from anywhere in this level,
press the key for a few seconds.
•1
Alarm 1 Trip Point
Alarm type: A1hP = High level alarm
A1LP = Low level alarm
A1hP
1001
A1H L = Latched high level alarm
A1LL = Latched low level alarm
A1Fr = Fast rate level alarm
A1Sr = Slow rate level alarm
[In engineering units or % of engineering span
per hour]
A1H YSt•2
1000
Alarm 1 Hysteresis
Not applicable to A1Frand A1Sralarm type.
[Process alarms – engineering units]
•1
Alarm 2 Trip Point
Alarm type
A2LP
[In engineering units or % of engineering span
per hour].
2002
A2H YSt•2
Alarm 2 Hysteresis
Not applicable to A2Frand A2Sralarm type.
[ in % engineering range]
200
A3hP
Continued on next page…
•1 Not displayed if the alarm is disabled ('None' selected) – see Section 4.3.2.
•2 Displayed only if custom alarm hysteresis is selected – see Section 4.3.2.
(not displayed for rate alarms).
13
8
…3 SET UP MODE
…3.2 Setup Level (Level 2)
•1
Alarm 3 Trip Point
Alarm type
A3hP
[In engineering units or % engineering span per
hour]
3003
A3 H YS•2
Alarm 3 Hysteresis
Not applicable to A3Frand A3Sralarm type.
[Process alarms – engineering units]
34 6
•3
Average Value
This is the mean average value of the process variable
input since the average was reset.
A14 05
•4
To reset the average value, select. rSt-Ythen press
rSt-n
the
key.
rSt-Y
rSt-n
–
–
reset
do not reset
L1308
Continued on next page…
•1 Not displayed if the alarm is disabled ('None' selected) – see Section 4.3.2.
•2 Displayed only if custom alarm hysteresis is selected – see Section 4.3.2.
(not displayed for rate alarms).
•3 The average value is reset automatically on power-up and can also be reset from
a digital input – see Section 4.3.3.
14
8
3
SET UP MODE…
…3.2 Set Up Level (Level 2)
•1
Maximum Value
This is the maximum value of the level input since the
maximum was reset.
H 1502
To reset the maximum value, select rSt-Ythen press
rSt-n
the
key.
rSt-Y
rSt-n
–
–
reset
do not reset
•1
Minimum Value
This is the minimum value of the level input since the
minimum was reset.
L1308
To reset the minimum value, select rSt-Ythen press
rSt-n
the
key.
rSt-Y
rSt-Y
–
–
reset
do not reset
Specific Gravity
SPGrAV
Enter the specific gravity of the liquid to be
measured.
1000
OAdJ
Offset Adjustment
An offset can be applied to the level input to enable spot
calibration or the removal of system errors.
[±10% of engineering range].
10
•1 The maximum and minimum values are reset automatically on power-up and can
also be reset from a digital input – see Section 4.3.3.
15
4
CONFIGURATION MODE
4.1 Introduction – Fig. 4.1
The Configuration Mode comprises two levels (3 and 4) as shown in Fig. 4.1.
Level 3 is divided into four frames. For most simple applications it is only necessary to
set up the parameters in the first frame.
Note.
When in the Configuration Level:
•
•
•
All the LED indicators flash.
All relays and logic outputs are turned off.
The analog output reverts to 0% (4mA) output level.
16
4
CONFIGURATION MODE…
…4.1 Introduction – Fig. 4.1
Level 4
LEVEL4
Engineering
ENG H I
Level 3
LEVEL3
Range High
Engineering
Hardware
A 1200
Configuration
ENG LO
Range Low
b 1200
C 1200
d 1200
Retransmission
Range High
rEt H I
Retransmission
rEt LO
Alarms and
E 0000
Set Points
Range Low
F 0000
G 0000
H 0000
Volume
VOLCON
Constant
Set-up
S-PASS
Operator
J
Password
Functions
K
Configuration
Password
C-PASS
L 0000
n
Modbus
Addr
Address
Digital
P 0000
Input and
r 0000
Serial
S 0000
Comms.
t 0000
Fig. 4.1 Configuration Levels
17
…4 CONFIGURATION MODE
4.2 Accessing the Configuration Mode
To access the Configuration Mode, enter the correct configuration code in
Level 1 – see Sections 2.2 to 2.4. The Configuration password is set up in Level 4.
4.3 Basic Hardware and Indicator Functions (Level 3)
4.3.1 Hardware Assignment and Input Type – Fig. 4.2
Level 3
LEVEL3
Note. To select this frame from anywhere in this level,
press the
key for a few seconds.
'ABCD' Settings
A 1200
b 1200
The first character (A, B, C or D) identifies the parameter
to be changed. The current setting is indicated by a
flashing letter. Parameter options are shown in Fig. 4.2.
C 1200
A
b
C
d
=
=
=
=
Hardware configuration
Input type and range
Not applicable
d 1200
No. of decimal points
Note. For custom settings contact the local distributor.
E 1203
Continued on page 20.
18
4
CONFIGURATION MODE…
…4.3.1 Hardware Assignment and Input Type – Fig. 4.2
A – Hardware Configuration
A 1200
Display
50Hz 60Hz
Relay 1
Source
Relay 2*
Source
Relay 3*
Source
Logic Output
Source
Analog Output
Source
1
A
Alarm 1
Alarm 1
Custom
Alarm 2
Alarm 2
Custom
Alarm 3
Alarm 3
Custom
IPFAIL
IPFAIL
Custom
ML
2
b
ML average
Custom
U
ML = Measured level
IPFAIL = Measured level failure
* only available if the appropriate option board is fitted
B – Input Type and Range Configuration
b 1200
Display
2
8
U
4 to 20 mA
1 to 10mA (P851, P861 sensor)
Custom configuration
C – Not Applicable
D – Process Variable
Display Decimal
Places
C 1200
d 1200
Display
Display
Temperature Units
0
1
2
3
4
xxxx
xxx x
xx xx
x xxx
x xxxx
0
Not applicable
Fig. 4.2 Hardware Configuration and Input/Output Ranges
19
…4 CONFIGURATION MODE
.3.2 Alarms – Figs. 4.3, 4.4, 4.5 and 4.6
All alarms output relays are de-energized in the alarm state (fail safe).
'EFGH' Settings
The first character (E, F, G or H) identifies the parameter
E 0000
to be changed. The current setting is indicated by a
flashing letter. Parameter options are shown in Fig. 4.3.
F 0000
G 0000
H 0000
E
F
G
H
=
=
=
=
Alarm 1 type
Alarm 2 type
Alarm 3 type
Alarm hysteresis
Note. For fail safe operation, active alarms denergize
the relay and inactive alarms energize the relay. For
custom settings contact the local distributor.
P 0000
Continued on page 25.
20
4
CONFIGURATION MODE…
…4.3.2 Alarms – Figs. 4.3, 4.4, 4.5 and 4.6
E – Alarm 1 Type
E 0000
Display
0
1
2
3
4
None
High Process
Low Process
High Latch
Low Latch
Fast Rate
Slow Rate
5
6
F – Alarm 2 Type
G – Alarm 3 Type
F 0000
G 0000
Display
Display
0
1
2
3
4
None
High Process
Low Process
High Latch
Low Latch
Fast Rate
0
1
2
3
4
None
High Process
Low Process
High Latch
Low Latch
Fast Rate
5
6
5
6
Slow Rate
Slow Rate
H – Alarm Hysteresis
h 0000
Display
0
1
2
3
4
5
6
U
None
0.1%
0.2%
0.5%
1.0%
2.0%
5.0%
Custom
Note. When custom alarm
hysteresis is selected, the
alarm hysteresis values must
first be set individually in the
Set Up Level – see Section 3.2
Value in % of
engineering range
See Note
Fig. 4.3 Alarm Types
21
…4 CONFIGURATION MODE
…4.3.2 Alarms – Figs. 4.3, 4.4, 4.5 and 4.6
Hysteresis
Trip
Point
Hysteresis
Process
Variable
Alarm On
Alarm Off
High Process
Alarm
On
Low Process
Alarm
Off
Note.
Process Alarms – an alarm becomes active when the process variable rises
above the high process alarm trip point value or falls below the low process
alarm trip point value. Process alarm trip point values are configured in
engineering units in Set Up Level (Level 2). If an alarm hysteresis value of
zero is configured the alarm becomes inactive when the process variable
value returns past the alarm trip point value. If a positive or negative
hysteresis value is configured the alarm becomes inactive when the process
variable reaches the hysteresis point. The hysteresis value is configured in
engineering units e.g. if a hysteresis point five inches H20 below the alarm
trip point is required, a hysteresis value of –5.0 is configured. The
programmable alarm hysteresis function can also be utilized for pump
control applications when an output relay is assigned to an alarm.
Fig. 4.4 Process Alarms
22
4
CONFIGURATION MODE…
…4.3.2 Alarms – Figs. 4.3, 4.4, 4.5 and 4.6
100
50
Hours
1
2
3
4
5
t (191 secs)
t (191 secs)
Alarm On
Alarm Off
Note.
Fast/Slow Rate Alarms – an alarm becomes active when the rate of change in
the process variable is faster or slower than the configured alarm value. Rate
of change alarm values are configured as a % of span change per hour. The
elapsed time period before the alarm condition is detected is dependant
upon the configured alarm value. This period can be calculated as follows:
1800
t = 10.81 +
trip value (as a % of eng. span/hr)
t = 191 seconds
The alarm remains active until the rate of change in the process variable
returns to the non-alarm condition. The calculated time period (t) elapses
between the process variable reaching the non-alarm condition and the
alarm becoming inactive.
Fig. 4.5 Rate Alarms
23
…4 CONFIGURATION MODE
PV
Alarm Trip
Value
Alarm Trip
Hysteresis
Alarm
Alarm
On
Latched
Alarm Off
Alarm
Acknowledgement
State
High Latch Alarm
PV
Alarm Trip
+ Hysteresis
Alarm Trip
Value
Alarm On
Alarm
Latched
Alarm
Off
Alarm
Acknowledgement
State
Low Latch Alarm
Note.
High/Low Latch Alarms – An alarm becomes active when the process variable
value rises above the high latch alarm trip point value or falls below the low
latch alarm trip point value. The latch alarm trip point values are configured
in engineering units in the Set Up Level (Level 2). The alarm remains active
until it is acknowledged and the alarm process condition is removed. The
alarm can be acknowledged using the keys on the instrument front panel
(see page 3) or via the volt-free digital input once it has been configured to
provide a remote alarm acknowledge facility.
Fig. 4.6 Latch Alarms
24
4
CONFIGURATION MODE…
4.3.3 Operator Functions – Fig. 4.7
'JKLN' Settings
The first character (J, K, L or N) identifies the parameter
J 0000
to be changed (indicated by a flashing letter). Available
parameter options are shown in Fig. 4.7 below.
K 0000
L 0000
n 0000
J
K
L
n
=
=
=
=
Not applicable
Not applicable
Operator Level frame enable
Operator Level math reset enable
Note. For custom settings contact the local distributor.
P0000
Continued on page 26.
L 0000
Parameter
Max./Min.
Average
Volume
Setting
0
1
2
3
4
5
6
7
✗
✗
✗
✗
✗
✗
✗
✗✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
✗
n 0000
Parameter
Setting
Max/Min./Average
0
1
✗
✗
Fig. 4.7 Operator Level Maths Reset Enable
25
…4 CONFIGURATION MODE
4.3.4 Digital Input and Serial Communications – Fig. 4.8 and 4.9
'PRST' Settings
P 0000
The first character (P, R, S or T) identifies the parameter
to be changed. The current setting is indicated by a
flashing letter. Parameter options are shown in Fig. 4.8.
r 0000
S 0000
P
r
S
t
=
=
=
=
Digital input function
Analog input filter
Serial communications configuration
Serial communications parity
t 0000
Note. For custom settings contact the local distributor.
LEVEL4
Continued on page 28.
Lock
Max
Unlock
Min
2
Front Panel Lock out
1
Average Max/Min Reset
Acknowledge
3
Alarm Acknowledge
Note.
Digital input options 1, 2 and 3 are edge-triggered to enable the front panel
keys to change the function when the digital input is operational.
Fig. 4.8 Digital Functions
26
4
CONFIGURATION MODE…
…4.3.4 Digital Input and Serial Communications – Fig. 4.8 and 4.9
P – Digital Input Function
R – Analog Input Filter
P 0000
r 0000
Display
Display
0
1
2
3
None
0
1
2
0 seconds
1 second
Average, Max/Min Reset
Front Panel Lockout
Alarm Acknowledge
2 seconds
5 seconds
10 seconds
20 seconds
40 seconds
60 seconds
5
A
B
C
D
S – Serial Communication
Configuration
T – Serial Communication
Parity
S 0000
t 0000
Display Baud Rate, 2/4 Wire
Display
0
1
2
3
4
Off
0
1
2
None
Odd
Even
2400, 2 Wire
2400, 4 Wire
9600, 2 Wire
9600, 4 Wire
Note. Settings for options P, S and T are available only if the appropriate
option board is fitted.
Fig. 4.9 Digital Functions and Serial Communications Configuration
27
…4 CONFIGURATION MODE…
4.4 Ranges and Passwords (Level 4)
Level 4
LEVEL4
Note. To select this frame from anywhere in this level,
press the key for a few seconds.
Engineering (Display) Range
ENG H I
High Value
(100.0 metres)
[–9999 to 99999]
1000
Low Value
(0.0 metres)
ENG LO
[–9999 to 99999]
00
Retransmission Range
Defines the engineering range to be retransmitted.
rEt H I
High (20mA output)
[–9999 to 99999 (in engineering units)]
Low (4mA output)
1000
rEt LO
[–9999 to 99999 (in engineering units)].
Continued on next page…
00
VOLCON
28
4
CONFIGURATION MODE
…4.4 Ranges and Passwords (Level 4)
Volume Constant – Fig. 4.10
This constant can be used to calculate the volume of
liquid in a tank from the measured level
VOLCON
S-PASS
C-PASS
Addr
[0.0 to 9999.9]
10
0
Set Up Password
The password enables access to the set up level
(Level 2).
[0 to 9999] Default/factory set = 0
Configuration Password
The password enables access to the configuration
levels (Levels 3 and 4). The Configuration password
overides the setup password.
0
[0 to 9999] Default/factory set = 0
•1
Modbus Address
This frame sets the Modbus address.
[1 to 99]
1
•1 Available only if the appropriate option board is fitted.
Cube:
Volume =
a x b x L
Cylinder:
Volume =
L
d
π x ( / )2 x L
L
2
Volume
=
Volume
Constant
=
Constant
a
a x b
π x ( / )2
d
b
d
Fig. 4.10 Volume Constant Calculations
2
29
5
INSTALLATION
EC Directive 89/336/EEC
In order to meet the requirements of the EC Directive 89/336/EEC for EMC
regulations, this product must not be used in a non-industrial environment.
End of Life Disposal
This instrument does not contain any substance that will cause undue harm to
the environment. It can therefore be safely considered as normal waste and
disposed of accordingly.
Cleaning
Clean the front panel only, using warm water and a mild detergent.
30
5
INSTALLATION…
5.1 Siting the System – Fig. 5.1
Notes.
DATUM L160
•
Sensor cable runs over long distances can
pick up transients which could impair
operation of the L160. Transient
protection within the L160 Level System
gives protection against induced voltage
transients of up to 2kV.
888888
•
In
high
humidity
environments,
condensation must be prevented from
entering any sensor vent (breather) tubes.
Structural support
Cable
Cable
restraint
Warning. In extreme/
hazardous
conditions,
e.g.
Borehole
Sensor
exposed areas with long cable
runs and instances of large
electrical surges, use commercial
high level transient protection.
Fig. 5.1 System Installation
31
…5 INSTALLATION
5.2 Siting the Instrment – Figs. 5.2 and 5.3
Close to Sensor
Minimum
Sensor
At Eye Level
Avoid Vibration
Fig. 5.2 Siting the Instrument – General Requirements
32
5
INSTALLATION…
…5.2 Siting the Instrument – Figs. 5.2 and 5.3
Temperature Limits
Environmental Limits
60°C
Max.
IP66
–10°C
Min.
NEMA4X
Humidity Limits
Use Screened Cable
0 to 90% RH
+
Warning. Select a location away from strong electrical and
magnetic fields. If this is not possible, particularly in applications where
mobile communications equipment is expected to be used, screened
cables within earthed metal conduit must be used.
Fig. 5.3 Environmental Requirements
33
…5 INSTALLATION
5.3 Mounting the Instrument – Figs. 5.4 and 5.5
The instrument is designed for wall-mounting or pipe-mounting (see Fig. 5.5). The
pipe-mounting kit (part no. 4600/0138) is suitable for both vertical and horizontal
pipes. Overall dimensions are shown in Fig. 5.4.
Dimensions in mm (in.)
161.5 (6.3)
250
(9.84)
200
(7.9)
69 (2.72)
Allowance for
Cable Bends
Fixing Holes
(x3) 6.5 (0.25) Dia
Fixing Centers
3
61(2 / ) O.D. Pipe
8
42 (1.65)
68 (2.68)
214
(8.43)
232
(9.13)
Vertical Pipe shown
for example only
Fig. 5.4 Overall Dimensions
34
5
INSTALLATION…
…5.3 Mounting the Instrument – Figs. 5.4 and 5.5
2
Drill suitable holes
Wall-mounting
Mark fixing centers (see Fig. 5.3)
1
3
Fix instrument to wall using suitable fixings
Position ‘U’ bolts on pipe
1
Position plates over ‘U’ bolts
2
Pipe-mounting
3
Secure plates
4
Secure transmitter to mounting plate
Fig. 5.5 Mounting Details
35
…5 INSTALLATION
5.4 Electrical Connections – Fig. 5.6
Warning.
•
The instrument is not fitted with a switch therefore a disconnecting device
such as a switch or circuit breaker conforming to local safety standards must
be fitted to the final installation. It must be mounted in close proximity to the
instrument within easy reach of the operator and must be marked clearly as
the disconnection device for the instrument
•
•
•
Remove all power from supply, relay and any powered control circuits and
high common mode voltages before accessing or making any connections.
Use cable appropriate for the load currents. The terminals accept cables up
to 14AWG (2.5mm2).
The instrument conforms to Mains Power Input Insulation Category 2,
Pollution Degree 2 (EN601010–1).
•
•
•
All connections to secondary circuits must have basic insulation.
After installation, there must be no access to live parts, e.g. terminals
Terminals for external circuits are for use only with equipment with no
accessible live parts.
•
•
If the instrument is used in a manner not specified by the Company, the
protection provided by the equipment may be impaired.
All equipment connected to the instrument's terminals must comply with
local safety standards (IEC 60950, EN601010–1).
Note.
•
Always route signal leads and power cables separately, preferably in earthed
(grounded) metal conduit.
•
It is strongly recommended that screened cable is used for signal inputs and
relay connections.
36
5
INSTALLATION…
Warning. Connect earth
(ground) wire and sensor screens
to chassis earth stud.
85 to 265V AC
Mains Supply
24V DC
Supply
or
+
–
L
N
1
2
1
2
Relay 3
Power Connections
N/O
C
N/C
Relay 1
RS485
N/O
C
N/C
TX– TX+
C
RX– RX+
3
4
5
6
7
8
9
10 11 12 13
14 15
16 17 18
N/O
Relay 2
19 20 21 22 23 24
+
–
C
N/C
Isig +3v 0vs –3vs
Logic
output
–
+
Analog
output
–
+
Logic
Input
Isig +3v 0vs –3vs
21 22 23 24
4
14
1
2
3
4
–
+
P871/P881 Sensor
P851/P861 Sensor
Make connections
via glands 1, 2 and 3
Sensor Connections
Sealed vent gland
(4) – do not use
Fig. 5.6 Electrical Connections
37
…5 INSTALLATION
5.5 Relays, Arc Suppression, Outputs and Input
5.5.1 Relay Contact Ratings
115/230V AC at 5A (non-inductive)
250V DC 25W max.
5.5.2 Arc Suppression
Arc suppression components are fitted to relays 2 and 3 only. If relay 1 is required to
switch inductive loads, fit the arc suppression components supplied.
5.5.3 Logic Output
18V DC at 20mA
Minimum load 900Ω
Isolation 500V from input (not isolated from retransmission output)
5.5.4 Retransmission Analog Output
Maximum load 15V (750Ω at 20mA)
Isolation 500V from input (not isolated from logic output).
5.5.5 Logic Input
Type: Volt-free
Minimum pulse: 250ms
38
SPECIFICATION
Operation
Display
High-intensity 7-segment, 1 x 5-digit LED display
Three alarm LED indicators
Display range
–9999 to +99999
±1 digit
14mm (0.56 in.)
Display resolution
Display height
Configuration
User-defined via front panel
Standard Functions
Alarms
Number
Three user-defined
Types
High/Low process
High/Low latch
Fast/Slow rate
Alarm hysteresis
0 to 100% of range
Math functions
Maximum and minimum value detection
Average level
SG correction
Tank volume calculation
20-breakpoint custom linearizer (factory configured)
39
…SPECIFICATION
Analog Inputs
Input type
1 to 10 mA, 4 to 20 mA or customize via PC Configurator
Input sampling rate
250ms
Accuracy
Indicator
0.2% of reading
<0.2% of span
Output
Sensor power supply
24V, 30mA max. (powers one 2-wire transmitter)
± 3V, 15mA (power for P851/P861 sensors)*
*Option board
Outputs – Standard Build
Retransmission
Analog, configurable in the range 4 to 20mA
Max. load
Isolation
15V (750Ω at 20mA)
500V DC from sensor input (not isolated from logic output)
Logic output
18V DC at 20mA
Min. load
Isolation
400Ω
500V from sensor input (not isolated from retransmission output)
Relay output
One relay as standard (SPDT) 5A at 115/230V AC, assignable to alarms
40
SPECIFICATION…
Options
One build can be selected from:
Type 01
Two relays + retransmission + logic output + digital input
(Standard Build)
Type 02
Type 03
Three relays + retransmission + logic output + digital input
Two relays + retransmission + logic output + digital input +
Modbus
Type 04
Two relays + logic output + retransmission +
P851/P861 power supply
I/O
Relay output
SPDT 5A at 115/230V AC
Assignable to alarms
Digital input
Type
Volt-free
250ms
Minimum pulse
Modbus serial communications
Connections RS422/RS485, 2- or 4-wire
Speed
2.4k or 9.6k baud rate
Modbus RTU slave
Protocol
Electrical
Voltage (supply)
85 to 265V AC 50/60Hz
24V DC optional
Power consumption
< 6VA (85 to 265V AC)
< 5W (24V DC)
Power interruption protection
<60ms/<3 cycles, no effect
>60ms/>3 cycles, instrument returns to operation after a controlled reset
41
…SPECIFICATION
Physical
Size
160mm wide x 250mm high x 68mm (6.3 in. wide x 9.84 in. high x 2.68 in.)
Weight
2kg (4.5lb)
Environmental
Operating limits
–10 to 55°C (14 to 131°F)
5 to 95% RH non-condensing
Temperature stability
<0.02% of reading or 2µV/°C (1µV/°F)
Front face
IP66 (NEMA 4X)
EMC
Emissions
Meets requirements of EN50081-2
Immunity
Meets requirements of EN50082-2
Design and manufacturing standards
CE mark
Electrical safety
EN61010-1
SS/L160 Issue 3
42
Customer Support
8
CUSTOMER SETUP LOG
We provide
a
comprehensive after sales
service via our Worldwide Service
Organization. Contact one of the following
offices for details of your nearest Service
and Repair Centre.
✍
LEVEL2
A1xx
United Kingdom
ABB Limited
Tel: +44 (0)1480 475321
Fax: +44 (0)1480 217948
LEVEL1
A1H YSt
A2xx
United States of America
ABB Inc.
Tel: +1 215 674 6000
Fax: +1 215 674 7183
CodE
A2H YSt
A3xx
A3H YSt
A xxxx
H xxxx
L xxxx
SPGrAV
0AdJ
Instrument Serial Number:
Client Warranty
L 1 6 0 /
/
Product Code:
Prior to installation, the equipment referred to in this manual must be stored in a clean,
dry environment, in accordance with the Company's published specification. Periodic
checks must be made on the equipment's condition.
In the event of a failure under warranty, the following documentation must be provided
as substantiation:
1. A listing evidencing process operation and alarm logs at time of failure.
2. Copies of operating and maintenance records relating to the alleged faulty unit.
CUSTOMER CONFIGURATION LOG
✍
LEVEL4
ENG H I
ENG LO
LEVEL3
A 1KC0
A
B
C
G
D
H
rEt H I
rEt LO
VOLCON
S-PASS
C-PASS
Addr
E 0000
E
F
J 0000
L
N
T
J
K
P 0000
ABB has Sales & Customer Support
expertise in over 100 countries worldwide
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
S
P
R
Printed in UK (03.06)
© ABB 2006